Id:
CVE-2017-7575
Comment
:
Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection password via a \x00\x01\x00\x00\x00\x05\x01\x5a\x00\x03\x00 request to the Modbus port (502/tcp). Subsequently the application may be arbitrarily downloaded, modified, and uploaded.
CVSSv2 Score:
5
Access vector:
|
NETWORK
|
Access complexity:
|
LOW
|
Authentication:
|
NONE
|
Confidentiality impact:
|
PARTIAL
|
Integrity impact:
|
NONE
|
Availability impact:
|
NONE
|
CVSSv2 Vector:
AV:N/AC:L/Au:N/C:P/I:N/A:N
CVSSv3 Score:
9.8
Attack vector:
|
NETWORK
|
Attack complexity:
|
LOW
|
Privileges required:
|
NONE
|
User interaction:
|
NONE
|
Scope:
|
UNCHANGED
|
Confidentiality impact:
|
HIGH
|
Integrity impact:
|
HIGH
|
Availability impact:
|
HIGH
|
CVSSv3 Vector:
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
References: