Id:
CVE-2017-7574
Comment
:
Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product.
CVSSv2 Score:
7.5
Access vector:
|
NETWORK
|
Access complexity:
|
LOW
|
Authentication:
|
NONE
|
Confidentiality impact:
|
PARTIAL
|
Integrity impact:
|
PARTIAL
|
Availability impact:
|
PARTIAL
|
CVSSv2 Vector:
AV:N/AC:L/Au:N/C:P/I:P/A:P
CVSSv3 Score:
9.8
Attack vector:
|
NETWORK
|
Attack complexity:
|
LOW
|
Privileges required:
|
NONE
|
User interaction:
|
NONE
|
Scope:
|
UNCHANGED
|
Confidentiality impact:
|
HIGH
|
Integrity impact:
|
HIGH
|
Availability impact:
|
HIGH
|
CVSSv3 Vector:
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
References: